Aiming at the complexity of dielectric relaxation response of transformer oil-paper insulation, a hybrid equivalent circuit new model was established to characterize the relaxation process of oil-paper insulation system according to the characteristics of oil-paper insulation. According to theory analysis of hybrid equivalent circuit, formula of the hybrid equivalent circuit parameters and the recovery voltage were deduced. Test data of a transformer recovery voltage was adopted to verify the method, and then the test data of a transformer before and after being maintained was used to diagnose transformer oil-paper insulation system based on hybrid equivalent circuit. The results show that: the return voltage curve which is gained by the hybrid equivalent circuit method inosculates very well with those gained by the field measurements, and the hybrid equivalent circuit can diagnose aging of transformer oil-paper insulation dielectric accurately. © 2016, Editorial Department of Electric Machines and Control. All right reserved.
Keyword:
Reprint 's Address:
Email:
Version:
Source :
Electric Machines and Control
ISSN: 1007-449X
CN: 23-1408/TM
Year: 2016
Issue: 3
Volume: 20
Page: 1-5
Cited Count:
SCOPUS Cited Count: 6
ESI Highly Cited Papers on the List: 0 Unfold All
WanFang Cited Count:
Chinese Cited Count:
30 Days PV: 2