Sun, Ying (Sun, Ying.) [1] (Scholars:孙颖) | Zheng, Jialong (Zheng, Jialong.) [2] | Zhuo, Weidong (Zhuo, Weidong.) [3] (Scholars:卓卫东) | Lin, Daojin (Lin, Daojin.) [4] | Su, Shaoling (Su, Shaoling.) [5]

Indexed by:

EI Scopus

Abstract:

This study considers the joint segment of the hybrid tower of Qiyun Bridge in Fu’an City as the research object to explore the mechanical characteristics of the hybrid tower joint segment of a cable-stayed bridge under eccentric load. It clarifies the mechanical performance and force transmission mechanism of the joint segment under eccentric load and the reasonable range of parameters affecting the force transmission efficiency using test and numerical analysis. The results indicated that the high safety coefficient, reliable working performance, and low stress level are the main characteristics of the bearing capacity of the hybrid tower joint segment with the rear bearing plate. The stress performance of the joint segment under the action of vertical eccentric load conforms to the force characteristics of eccentric compression components, and the strain is symmetrically distributed in the section. The bearing plate and the shear connector play a vital role in the load transfer, as demonstrated by the strain change of the steel plate (shell) near the bearing plate, and the shear force borne by the shear key near the bearing plate is greater than that of the stud shear key. In addition, the vertical load is effectively transmitted in the joint segment. The transfer efficiency of the load in the joint segment is greatly affected by the thickness of the bearing plate and the shear stiffness of the shear connector. The transfer efficiency increases initially and then tends to stabilize with the increase in the thickness of the bearing plate or the shear stiffness of the shear connector. When the shear key stiffness increases to more than 10 times the original design shear stiffness or the thickness of the bearing plate exceeds 16 mm, the load transfer efficiency remains basically unchanged. In addition, there is an apparent transmission length within the joint segment, which is about 3 m. Beyond this length, the bearing ratio of the steel shell and the filled concrete is basically close to the section stiffness ratio of the joint segment. The steel shell and the concrete, respectively, bear about 50% of the vertical load after the force transfer. The research results provide guidance and reference for the design of similar projects. © 2025 Sichuan University. All rights reserved.

Keyword:

Bridge cables

Community:

  • [ 1 ] [Sun, Ying]College of Civil Engineering, Fuzhou University, Fuzhou; 350108, China
  • [ 2 ] [Zheng, Jialong]College of Civil Engineering, Fuzhou University, Fuzhou; 350108, China
  • [ 3 ] [Zhuo, Weidong]College of Civil Engineering, Fuzhou University, Fuzhou; 350108, China
  • [ 4 ] [Lin, Daojin]China Communications Highway Planning and Design Institute Company Limited, Beijing; 100088, China
  • [ 5 ] [Su, Shaoling]Fu’an City Construction Management Company Limited, Ningde; 355099, China

Reprint 's Address:

  • 卓卫东

    [zhuo, weidong]college of civil engineering, fuzhou university, fuzhou; 350108, china

Show more details

Related Keywords:

Related Article:

Source :

Advanced Engineering Sciences

ISSN: 2096-3246

Year: 2025

Issue: 3

Volume: 57

Page: 171-183

Cited Count:

WoS CC Cited Count:

SCOPUS Cited Count:

ESI Highly Cited Papers on the List: 0 Unfold All

WanFang Cited Count:

Chinese Cited Count:

30 Days PV: 3

Online/Total:735/10361266
Address:FZU Library(No.2 Xuyuan Road, Fuzhou, Fujian, PRC Post Code:350116) Contact Us:0591-22865326
Copyright:FZU Library Technical Support:Beijing Aegean Software Co., Ltd. 闽ICP备05005463号-1